What to do if Tecnoware UPS is overloaded?
- RrubiofranklinAug 15, 2025
If the Tecnoware UPS is overloaded, you should remove some of the connected devices from the UPS output.
What to do if Tecnoware UPS is overloaded?
If the Tecnoware UPS is overloaded, you should remove some of the connected devices from the UPS output.
What to do if Tecnoware EVO DSP PLUS MM 3.6 UPS shows fault code 14?
If the Tecnoware UPS displays fault code 14, accompanied by a lit icon and continuous beeping, it indicates a short circuit on the UPS output. Check the output wiring and the connected devices for any short circuit.
How to unlock Tecnoware EVO DSP PLUS MM 3.6 from Bypass mode?
If your Tecnoware UPS is locked in Bypass mode after repetitive overloads, first remove the excess loads from the UPS output. Then, shut down the UPS and restart it.
Why is my Tecnoware UPS beeping twice every second?
If the icons are flashing on the LCD display of your Tecnoware UPS and the alarm beeps twice every second, it means the UPS is overloaded. Remove some of the loads from the UPS output.
What does fault code 43 mean on a Tecnoware UPS?
If fault code 43 is displayed on your Tecnoware UPS, accompanied by a lit icon on the LCD and continuous beeping, it means the UPS was overloaded for too long and has become faulty, causing it to shut down automatically. Remove the excess loads from the UPS output and restart it.
Why Tecnoware EVO DSP PLUS MM 3.6 battery backup time is short?
If your Tecnoware UPS battery backup time is shorter than expected, charge the batteries for at least 4 hours and then check the capacity. If the problem persists, contact Technical Service.
Why Tecnoware EVO DSP PLUS MM 3.6 has no display?
If there is no indication or alarm on the front panel of your Tecnoware UPS, and the graphic display is off, check the following: * Ensure the input cable is firmly connected to both the AC input mains and the UPS AC input socket. * Check the input circuit breaker. If it is off, push the external button to reactivate it.
What does it mean when Tecnoware EVO DSP PLUS MM 3.6 displays fault code 1, 2, 3, 4, 11, 12, 13 or 41?
If fault code 1, 2, 3, 4, 11, 12, 13 or 41 is shown on the LCD display of your Tecnoware UPS and the alarm beeps continuously, contact Technical Service, as a UPS internal fault has occurred.
Why is Tecnoware EVO DSP PLUS MM 3.6 beeping and the icon is flashing?
If the icons are flashing on the LCD display and the alarm beeps every second on your Tecnoware UPS, it indicates that the external or internal batteries are incorrectly connected. Check if all batteries are connected correctly.
Essential safety guidelines for installation, operation, and maintenance of the UPS.
Essential safety standards, circuit breaker recommendations, and cable usage for UPS installation.
Steps to ensure the UPS is safe to install, including input voltage removal and proper grounding.
Step-by-step guide for connecting the UPS to AC power and connecting output devices.
Ensures devices are off and AC input is restored before turning on the UPS.
Guides through the self-test, simulating blackout, and observing mode transitions.
Instructions for connecting devices and initial battery charging for optimal performance.
Details fatal error indicators, fault codes, and emergency disconnection advice.
Addresses issues where the UPS shows no signs of life or activity on the front panel.
Guides on interpreting flashing icons and beeping alarms indicating operational problems.
Troubleshooting steps for battery-related faults, low voltage warnings, and charger issues.
Resolving issues related to overload conditions, short circuits, and device protection.
Troubleshooting internal UPS faults, battery capacity degradation, and fan/temperature issues.
| Apparent Power | 3600VA |
|---|---|
| Battery Capacity | 9Ah |
| Number of Batteries | 6 |
| Battery Voltage | 12V |
| Frequency | 50/60 Hz |
| Transfer Time | 0 ms |
| Communication Interface | USB, RS232 |
| Operating Temperature | 0-40°C |
| Humidity | 0-95% non-condensing |
| Input Voltage | 230 VAC |
| Output Voltage | 230V |
| Battery Type | Sealed Lead Acid |
| Topology | Double Conversion Online |
| Waveform | Sinewave |
| Protection | Overload, Short Circuit |
| Power Rating | 3600 VA / 2880 W |