Remote speed reference and Remote run
1) Ensure that you have carried out installation & wiring requirements as
per step1 quick start guide on previous page before you proceed.
2) For analogue signal type. -10V to +10V or 0-10V dc. Use the terminal
AI1 or AI2. Set SW2 in V position.
For analogue input type 4 -20mA. Use the terminal AI2. Set SW2 to I
Position. ( default).
. Connect remote potentiometer OR remote 0-10 vdc signal as required.
to terminals AI1 Or AI2.
Functions of AI1 & AI2 can be set by parameter 04-00 & 04-05.
Terminal + 12Vdc & -12Vdc is the supply provided for use with the
potentiometer.
Terminals AI1 &AI2 are for potentiometer wiper connection.
Terminal GND is 0Vdc.
3) Connect remote start switch if required according to diagram in the
instruction manual.
Use terminals +24Vdc & S1 (Forward run).
Use terminals +24Vdc & S2 (Reverse run)
Step 1
Remote mode wiring. Speed reference and Run signals.
Step 2
Remote mode Run
1) Power up.
Display will read the frequency from one of the following according to the
Connection made to AI1 or AI2 terminal. Set parameter 00-05 =0001
a) Remote external potentiometer
b) Remote 0-10VDC analog signal.
Step 3
Check/ verify and alter parameters
Check / verify and alter parameters for remote start & remote frequency
as necessary before you proceed. Parameters 00-02 & 00=05
See quick start parameter list & How to alter parameters.