Page 8 of 10 11/07/14
SLV & SV mode set parameters in parameter Group 17.
Three auto tune modes are available. Rotational/ Static & Resistance.
Selected by parameter 17-00
Use rotational where possible. Motor rotates the process takes about 50 secs
Use Static when rotation of load is not possible. It takes about 35 secs.
Use line to Line resistance for long cable ( above 50 meters in V/f mode)
Motor parameters in Group 2 are automatically set when performing an auto-tune (17-10=1).
In most cases no adjustment is required after performing an auto-tune except when using the
inverter in special applications (e.g. machine tool, positioning, etc…).
Enable auto tune function by parameter 17-10 =1.
Press RUN button to activate ( after display showing “atredy”). Once successful the display
will show end. If AtErr is shown check parameter 17-11 to identify the reason.
0: No error
1: Motor data error
2: stator resistance tuning error
3:leakage induction tuning error
4: Rotor resistance tuning error
5: mutual induction tuning error
6: encoder error
7: DT Error
8: Motor’s acceleration error
9: Warning