EasyManua.ls Logo

TECO A510 - Advanced Control Modes and Tuning; Control Modes & Auto Tune; V;f Mode Parameters

TECO A510
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 7 of 10 11/07/14
Control Modes & Auto Tune
A510 provides five control modes
Select the relevant control mode for the application.
Default control mode is V/f.
V/f can be used for most applications specifically multi-motor
or applications where auto tune is not successful
or when a customized v/f pattern may be required.
Several V/f patterns are available selectable by parameter 01-00.
select the appropriate one based on the application load type and the motor base frequency of
50 or 60 Hz.
For selections of the V/f patterns . Refer to the instruction manual.
For Vector modes SLV & SV modes are used for obtaining best performance
from a motor and in applications that require dynamic response to torque and speed change
use SV + Encoder.
V/f Mode Parameters:-
Parameter
Default
Range
Note
01-00
F
0-FF
F= General Purpose. 60 Hz. system
0= General Purpose . 50Hz. System
For full list of preset patterns set by 01-
00,refer to the manual.
FF= Customized V/f.
Set parameters 01-02 to 01-13.
For Motor1 parameters in V/f mode, set the name plate data in parameters 02-00 to 02-19
Parameters 02-09 to 02-19. Not normally need to be adjusted.
Note:- Two independent set of parameters can be set. Motor 1 & Mmotor2.
Parameters 02-20 to 02-26. ( Motor 2 can only function in V/f mode).

Related product manuals