3-10
Item
E310
Communication Control
1. Control by RS485
2. One to one or one to many control.
3. BAUD RATE/STOP BIT/PARITY/bit can be set
Braking Torque
About 20, the model below 20HP with built-in braking
transistor and the specified external braking resistors can provide
100%
Operation temperature
14-120(-10 ~ 50)
Storage temperature
4-140(-20 ~ 60)
Humidity
0 – 95% Relative Humidity(Non-condense)
Vibration
1G (9.8m/
2
S )
Enclosure
IP20
Protective Functions
Overload protection
The relays to protect the motor (the curve can be set) and the
inverter (150 % / 1min)
Over Voltage
200V class: DC Voltage
410V 400Vclass: DC Voltage820V
Under Voltage
200V class: DC Voltage
190V 400Vclass: DC Voltage380V
Momentary Power
Loss Restart
Restart can be initiated with spin start after momentary power loss
in Max 2 sec.
Stall Prevention
Stall prevention for Acceleration/ Deceleration/ Operation.
Short-circuit output
terminal
Electronic Circuit Protection
Grounding Fault
Electronic Circuit Protection
Other Function
Protection for overheating of heat sink, over torque detection,
error contact control, reverse prohibit, prohibit for direct start
after power up and error recovery, parameter lock up.