TECO E310-201-H - Figure 5-4 Motor RUN Failure Flow Chart

TECO E310-201-H
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-9
Is MCCB
applied?
Can MCCB be
applied?
Are voltages
between power
terminals correct?
Is LED lit?
Are there outputs between the
U-V-W terminals of the motor?
Are outputs between U-
V-W even
Short circuited wiring
The power is abnormal
Incorrect wiring
E310fault
The operation switch is set to
“RUN’ position
E310fault
E310fault
YES (within ±3% of the normal value)
YES (voltage deviation between output pairs are even if
within ±3% of the normal value without the motor
Motor
Motor faults
Incorrect wiring
YES
YES
N
O
N
O
N
O
Is the operation switch
in “RUN’ ?
N
O
N
O
N
O
N
O
The motor can not run
z Figure 5-4 Motor RUN failure Flow chart