4-11 
07-Protection function group 
Function 
Code No. 
Description Range/Code 
Factory
Setting
Remarks
07-00 Trip Prevention Selection 
xxxx0 :
 Enable Trip Prevention During 
Acceleration 
xxxx1 :
 Disable Trip Prevention During 
Acceleration 
xxx0x :
 Enable Trip Prevention During 
Deceleration 
xxx1x :
 Disable Trip Prevention During 
Deceleration 
xx0xx :
 Enable Trip Prevention in Run Mode 
xx1xx :
 Disable Trip Prevention in 
Run Mode 
x0xxx : Enable over voltage Prevention in 
Run Mode 
x1xxx : Disable over voltage Prevention in 
Run Mode 
00000  
07-01 
Trip Prevention Level During 
Acceleration (%) 
50 ~ 200  200 
Inverter 
Rated 
Current
200%
07-02 
Trip Prevention Level During
 
Deceleration (%) 
50 ~ 200  200 
Inverter 
Rated 
Current
200%
07-03 
Trip Prevention Level In Run
 Mode 
(%) 
50 ~ 200  200 
Inverter 
Rated 
Current
200%
07-04 
over voltage Prevention Level in Run 
Mode  
350.0 VDC ~ 390.0 VDC 
700.0 VDC ~ 780.0 VDC 
380.0/ 
760.0 
 
07-05 
Electronic Motor Overload Protection 
Operation Mode 
0 : Enable Electronic Motor 
Overload Protection 
1 : Disable Electronic Motor 
Overload Protection 
1  
07-06  Motor type Selection 
0 : Electronic Motor Overload Protection Set 
for Non-Inverter Duty Motor 
1 : Electronic Motor Overload Protection Set 
for Inverter Duty Motor 
0  
07-07 
Motor Overload Protection 
Curve Selection 
0 : Constant Torque (OL =103 %)   
(150 % for 1 Minute) 
1 :
 Variable Torque (OL = 113 %) 
  (123 % for 1 Minute) 
0   
07-08 
Operation After Overload Protection is 
Activated 
0 : Coast-to-Stop After Overload   
Protection is Activated 
1 : Drive Will Not Trip when Overload 
Protection is Activated (OL1) 
0   
07-09 
Over torque Detection Selection 
(OL3) 
0 : Disable Over torque Operation 
1 : Enable Over torque Operation   
Only if at Set Frequency 
2 : Enable Over torque Operation   
while the Drive is in Run Mode 
0