4 Challenger10 Installation and Quick Programming Manual
Power supply to RS-485 LAN devices
Devices on the LANs may be supplied from the panel’s or DGP’s + and LAN
power terminals. Use an external 12 V power supply (such as TS0073 2 A Power
Supply) when:
the device is more than 100 m (data cable length) from the panel
electrical isolation is required
more power is needed than can be provided by the LANs
When powering a LAN device from an external 12 V power supply:
Connect the external power supply’s ‘+’ terminal to the device’s ‘+’ terminal.
Do not connect the power supply + to the LAN +.
Connect the external power supply’s ‘-’ terminal to the device ‘-’ terminal.
Connect the LAN cable black wire ‘-’ to the device ‘-’ terminal.