For this setting the zero point will be converted to 4 mA and the value
zero point + range to 20 mA; intermediate values will be converted
proportionally.
An underflow of the zero point will result in the output current sinking
linearly to a minimum of 0 mA (-25 % of the measurement range).
Further underflows cannot be evaluated (output 0 mA). On overflow
of the zero point + range value, the output current will rise linearly to a
maximum of 21.5 mA (about 110 % of the measurement range). Further
rises cannot be evaluated (output about 21.5 mA).