6.5.2 Fault current
The following table shows what the current output is during a fault,
depending on the settings:
21,5 mA
with short-circuit
21,5 mA
with short-circuit
22 mA
with short-circuit
(not distinguishable from
End value overrange)
0 mA
with lead breakage
(not distinguishable
from Start value
measurement)
2,0 mA
with lead
breakage
0 mA
with lead breakage
(not distinguishable from
Start value measurement)
Last measured value before the fault
22 mA
(not distinguishable from
End value overrange)
0 mA
(not distinguishable
from
Start value
measurement)
0 mA
(not distinguishable from
Start value measurement)
6.5.3 Fault current
Please note when entering Start value and End value:
• Both values are to be entered in the units, which were selected under
Units (section 6.2).
• Values between 0 mA and 20 mA can be entered, or between the
values of these limits converted into the selected units, using the
parameters Zero point and Conversion factor see section 6.3.2 The
difference between End value and Start value must be at least 1 % of the
End value (preset automatically by the Transmitter Power Supply).