EasyManua.ls Logo

Tecsis EGS80X002001 - Page 44

Tecsis EGS80X002001
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Betriebsanleitung/Operating manual
EGS80X002001
44 BD_BE 987 b www.tecsis.de
6.5.2 Fault current
The following table shows what the current output is during a fault,
depending on the settings:
Setting
0 mA ... 20mA
4 mA ... 20 mA
NE43
4 mA ... 20mA
Up/Down
21,5 mA
with short-circuit
21,5 mA
with short-circuit
22 mA
with short-circuit
(not distinguishable from
End value overrange)
0 mA
with lead breakage
(not distinguishable
from Start value
measurement)
2,0 mA
with lead
breakage
0 mA
with lead breakage
(not distinguishable from
Start value measurement)
Hold
Last measured value before the fault
Max
21,5 mA
21,5 mA
22 mA
(not distinguishable from
End value overrange)
Min
0 mA
(not distinguishable
from
Start value
measurement)
2,0 mA
0 mA
(not distinguishable from
Start value measurement)
6.5.3 Fault current
Please note when entering Start value and End value:
• Both values are to be entered in the units, which were selected under
Units (section 6.2).
• Values between 0 mA and 20 mA can be entered, or between the
values of these limits converted into the selected units, using the
parameters Zero point and Conversion factor see section 6.3.2 The
difference between End value and Start value must be at least 1 % of the
End value (preset automatically by the Transmitter Power Supply).