POWER SUPPLY 
 
The NT935-4 control unit has UNIVERSAL power supply, i.e. it can be supplied by 24 to 240 Vac-Vdc, 50/60Hz irrespectively 
of polarity in Vdc (terminals 40-42).  
 
This is obtained thanks to the use of a tested power supply unit, newly designed and manufactured, that frees installers from 
worrying about the correct Vac and Vdc supply. 
 
 
The ground must always be connected to terminal 41. 
 
When  the  unit  is  supplied  directly  by  the  secondary  of  the  transformer  to  protect,  it  can  be  burnt  out  by  strong 
overvoltages. 
This happens if the main switch is closed and the transformer has no load (blank test). 
The above-mentioned problems are much more evident when the 220 Vac voltage is taken directly from the transformer 
secondary bars and there is a fixed capacitor battery to phase the transformer itself. 
 
 
To protect the  control unit from  line overvoltages,  we  suggest using the  PT-73- 220  electronic discharger, designed by 
TECSYSTEM S.r.l. for this specific purpose. As an alternative we suggest using 110 Vac or, even better, 110 Vdc supply 
voltages. 
  
 
If  an  existing  control  unit  must  be  replaced  with  a  new  one,  to  guarantee  its  correct  and  safe  operation,  the 
sensor/relay/supply connecting terminals must be replaced with the new terminals supplied. 
 
 
ALARMS AND VENTILATION 
 
Carry out the electrical connections on the removable terminal blocks only after disconnecting them from the unit. 
When the control unit is in one of the modes mentioned below, it does not monitor the temperature and the relays are all 
blocked, The fault contact switches and the fault LED flashes. 
  
 Vis. programming display 
 PRG programming 
 Relay test 
 
The ALARM and TRIP relays switch only when the set temperature thresholds are exceeded. 
 
The FAULT contact, programmed in failsafe mode (default YES), opens (11-12) when the equipment is supplied only if 
the unit detects no fault on switching on, and stays in this condition until one of the following events occurs: 
 
 Data memory fault (Ech message). 
 Pt100 sensor fault (FCC short-circuited sensor, FOC interrupted sensor or Fcd quick temperature increase)  
 CAL damage to the measurement circuit. 
 Insufficient supply voltage. 
 During the power on reset after programming (PRG), displaying the data (VIS) and test relay.  
 
The FAULT failsafe can be disabled selecting FAULT failsafe "NO" see step 30-31 programming page 15. 
 
NOTE: do not connect the FAULT relay to the transformer tripping circuit to avoid unwanted system interruptions. 
 
 
FAULT AND RESET MESSAGE SEQUENCE  
 
Find below the sequence of fault messages and RESET function condition. 
 
1) ECH         
2) CAL            
3) FCD                  
4) ERR PT 
  
 
  
 
The FAN1 and FAN2 contacts can be used to control the cooling fans, or they can be inserted in the conditioning system of 
the transformer room, see paragraph Fan control on page 18.  
 
NOTE: always disconnect the unit before performing any electrical connections. 
 
 
FAULT 11-12 NC: ALARM FAULT OR POWER OFF 
FAULT 11-12 NO: POWER ON OR NO FAULT  
FAULT CONTACT OPERATION (failsafe enabled) 
 
  
  
eeprom fault                        
measurement circuit fault                       
quick temp. increase fault               
FCC or FOC sensor fault                        
 
 
erasable message 
erasable message 
resettable condition                  
non-resettable condition