The  control  unit  does  not  switch  on  and  the 
supply to terminals 40-42 is correct. 
Check that: the connector is correctly inserted into its housing, the 
wires  are  tightened,  there  is  no  evidence  of  burning  on  the 
connectors. Disconnect the power supply, carry out the above and 
reconnect. 
One  of  the  four  channels  is  in  FAULT  due  to 
FOC/FCC 
Check the connections of the Pt100 sensors, check the instructions 
given  in  the  paragraphs:  measurement  signal  transfer  and 
temperature sensor diagnostics on page 16-17. 
When turning on, the display shows “ECH” 
Strong interference has  damaged the stored data.  See  the 
paragraph Programmed data diagnostics on page 16.  
All the PT100 sensors are in FCC. 
Incorrect sensor connection, the terminal block has been inserted 
upside down. Check the connections and the terminal board. 
The  temperature  shown  by  one  or  more 
channels is wrong. 
Contact the TECSYSTEM Technical Department. 
Sudden trip of the main switch. The temperature 
is  on  standard  levels.  Just  one  channel  has 
caused the trip. 
Check the temperatures recorded in T-MAX, check the instructions 
given  in  the  paragraphs:  measurement  signal  transfer  and 
temperature  sensor  diagnostics  on  page  16.  Activate  the  FCD 
function. 
See the FCD function on page 28. 
Contact TECSYSTEM Technical Department if the problem persists. 
European  directives  2012/19/EC  (WEEE)  and  2011/65/EC  (RoHS)  have  been  approved  to  reduce  electrical  and 
electronic waste and promote the recycling and reuse of the materials and components of said equipment, cutting down 
on the disposal of the residues and harmful components of electrical and electronic materials. 
  
All the electrical and electronic equipment supplied after 13 August 2005 is marked with this symbol, pursuant to 
European  directive  2002/96/EEC  on  electrical  and  electronic  waste  (WEEE).  Any  electrical  or  electronic 
equipment marked with this symbol must be disposed of separately from normal domestic waste. 
 
Returning  used  electrical  devices:  contact  TECSYSTEM  or  your  TECSYSTEM  agent  for  information  on  the  correct 
disposal of the devices. 
 
TECSYSTEM is aware of the impact its products have on the environment and asks its customers active support in the 
correct and environmentally-friendly disposal of its devices. 
 
 
TECHNICAL INFORMATION : ufficiotecnico@tecsystem.it 
 
SALES INFORMATION : info@tecsystem.it