EasyManua.ls Logo

Tek-Air VorTek VT-7000 series - Page 23

Default Icon
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23VORTEK Doc.# VT5 OM 050499, Rel. 2.1
Appendices Appendix A
Engineering Department
43 Beaver Brook Road
Danbury, CT 06810
(203) 791-1400 Phone
(203) 798-6534 Fax
Installation Drawing
VorTek
Oval Duct Insertion Probes
Revision Letter: B
Dwg. No:
Revision Date: 4/2/97
Filename: VT5300G.CDR
Drawn By: GV
For Qty. Of Sensors Per Probe
See Schedule.
Typical Sensor
Probe Bar
For Qty. Of Probes
See Schedule
Shedder Bar
Sensor Clamp
Shroud
H
A1
5/16" Dia. Hole To
Receive Probe Support
End (Typical).
A2
A3
A4
MOUNTING RECEIVING
Bottom View
MOUNTING INSERTION
Top View
3 3/4" Dia Hole In
Ductwork For
Insertion Of Probe
Sensor Enclosure And
Connection Cable Receptacle
(includes Integral Gasket)
#10 Tek
Screw (typ.)
W
A
A
Inlet View
Slot In Rod To Be
Aligned With Airflow
Direction
Section A-A
Probe Alignment Slot
Req'd For All Bars
Selection of Materials For Construction
Aluminum
& ABS
CPVC
& ABS
304 St Steel High Temp.
St. Steel
NOTES:
1. Install In Accordance With Airflow Direction
Indicator.
2. For Qty. Of Probes & Sensors Per Probe, See Schedule.
3. For Units With 2 Probes, Use Locations A1 & A3 Only.
4. Probes 14" Long Or Less Are Capped With No Studs Or
Nuts Provided. In This Case, No (5/16") Hole Should
Be Drilled.
4“X4”X2 1/2”
5/16“ Threaded Rod
with Jam Nuts
(provided)
See Note 4
For Applicable
Hole Locations
See Schedule.
Airflow
Airflow
A-4A-4