EasyManua.ls Logo

Tekmar 284 - EMS, Modbus & BACnet Connections; EMS Connection

Tekmar 284
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2016 284_D - 05/16
29 of 60
A Watts Water Technologies Company
5V
dc
Out
Pressure
Sensor
In
+
14
Vdc
-
15
Gnd
13
Wiring a Pressure Sensor Terminals 13 to 15
An analog pressure sensor can be connected to the 284 to provide water pressure monitoring. The
control supports a V (dc) style pressure sensor with a signal range of 0.5 to 4.5 V (dc). Examples
of compatible aftermarket pressure sensors include the Honeywell PX2 (AA) series and the
Measurement Specialties 7100 series.
Connect one wire from the power supply (+5 VDC) on the pressure sensor to the 5V dc Out
terminal 13.
Connect one wire from the pressure signal on the pressure sensor to the Vdc (+) In terminal 14.
Connect one wire from the GND (0V) on the pressure sensor to the Gnd (-) terminal 15.
No Power
Boil
In
Vent
23 24 25
Com
Wiring a Vent Sensor Terminals 23, 25
A vent sensor can be connected to the 284 to provide monitoring of the common boiler plant exhaust vent temperature.
Compatible sensors include a 10K ohm NTC curve J thermistor.
The control is capable of displaying temperatures up
to 500°F (260°C).
The vent sensor can also be used to provide a vent temperature limiting feature.
Connect one wire from the vent sensor to the Vent terminal 23.
Connect the second wire to the Com terminal 25.
+
-
EMS
No Power
Com
Out
17
Boil
Sup
18
-
19
In
EMS
+
16
EMS Connection Terminals 16, 19
Modbus
®
Connection Terminals 40 to 42
BACnet
®
Connection RJ45 Plug
A Building Automation System (BAS) can be connected to the 284 for remote
monitoring & adjustment capability. BACnet
®
IP communications use an
ethernet socket. Use a CAT-5E or CAT-6 cable. The maximum recommended
cable length for CAT-5E is
150 ft. (45.7 m)
&
300 ft. (91.4 m)
for CAT-6.
Connect the Ethernet RJ45 socket on the BACnet
®
IP network to the
Ethernet RJ45 socket on the 284.
A Building Automation System (BAS) can be connected to the 284 for remote monitoring
& adjustment capability. Modbus
®
communications use an RS 485 connection. Use
18 AWG Twisted Shielded Pair cable. Cable length is dependent on the baud rate &
whether or not terminating resistors are used. Refer to the BAS Integration Manual
284_B for details on the maximum recommended cable length.
Connect the B (+) terminal on the BAS network to the RS 485 B (+) terminal 40.
Connect the A (-) terminal on the BAS network to the RS 485 A (-) terminal 41.
Connect the ground (G) terminal on the BAS network to the Gnd terminal 42.
An Energy Management System (EMS) can be connected to the 284 to provide a target water
temperature. Either a 0 to 10 V (dc) or 2 to 10 V (dc) signal may be used.
Connect one wire from the EMS to the EMS (+) In terminal 16.
Connect a second wire from the EMS to the Com (-) terminal 19.
A 0 - 20 mA signal can be converted to a 0 - 10 V (dc) signal by installing a 500 Ω resistor in
parallel between the Com (-) & EMS (+) In terminals (19 & 16). The EMS Signal setting must
be set to 0-10.
RJ45
BACnet
Network
Switch
Boiler
Control 284
EMS, Modbus
®
& BACnet
®
Connections
BAG
Master
284
40 41 42
Gnd
+–
RS 485
BA
(+)
(-)
A 4 - 20 mA signal can be converted to a 2 - 10 V (dc) signal by installing a 500 Ω resistor in parallel between the Com (-) &
EMS (+) In terminals (19 & 16). The EMS Signal setting must be set to 2-10.
The APP MODE setting in the Setup Menu must be set to EMS.

Other manuals for Tekmar 284

Related product manuals