Installation & Operation Manual
1 of 48 © 2016 680_D - 05/16
Features
BACnet or Modbus communication
Automatic snow/ice detection
Supports both in-slab and retrofit aerial sensors
Tandem snow/ice detection
Energy monitoring
Idling
Storm
EconoMelt
Warm weather shut down
Cold weather cut off
Slab protection
Exercising
Introduction
The Snow Melting Control 680 is designed to operate electric or hydronic equipment to melt snow or ice from any surface
including driveways, walkways, business entrances, parking ramps, loading docks, hospital entrances, helipads and car
wash bays. It communicates with Building Automation Systems using BACnet
®
or Modbus
®
for alert notification, remote
monitoring and adjustment capability. The 680 uses a tekmar Snow/Ice Sensor 090 or a Snow Sensor 095 to automatically
detect snow or ice on the snow melting slab. Up to two snow/ice sensors can be installed, thereby increasing detection area
and providing backup redundancy in the case of sensor failure. Upon detection of snow or ice, the 680 operates electric
heating cable, a single hydronic condensing or non-condensing boiler, or a steam valve to provide heat to the snow melt
load. The 680 provides boiler return protection by operating a mixing valve or variable speed injection mixing. Monitoring
of energy consumption is possible when it is connected to an optional flow sensor.
BACnet is a registered trademark of ASHRAE. ASHRAE
does not endorse, approve or test products for
compliance with ASHRAE standards. Compliance of
listed products to the requirements of ASHRAE Standard
135 is the responsibility of BACnet International (BI).
BTL is a registered trademark of BI.

Table of Contents

Questions and Answers

  • M
    Michele HicksSep 4, 2025
    How to resolve 'BOILER RETURN SENSOR SHORT CIRCUIT ERROR' on Tekmar 680 Melting Machines?
    • V
      Victoria JonesSep 4, 2025
      The control is unable to read the Boiler Return Sensor 082 on terminals 8 and 10 because there is a short circuit. Check the boiler return sensor wire for short circuits according to the sensor installation manual. If needed, replace the boiler return sensor.
  • J
    jessicasteeleSep 3, 2025
    What should I do if my Tekmar 680 Melting Machines displays a 'BOILER RETURN SENSOR OPEN CIRCUIT ERROR'?
    • J
      Jeffrey SanchezSep 3, 2025
      The control cannot read the Boiler Return Sensor 082 on terminals 8 and 10 because of an open circuit. Check the boiler return sensor wire for open circuits according to the sensor installation manual. It may be necessary to replace the boiler return sensor.
  • J
    Jonathon FordSep 2, 2025
    How do I troubleshoot a 'BOILER SUPPLY SENSOR SHORT CIRCUIT ERROR' on a Tekmar Melting Machines?
    • A
      Alexis PughSep 2, 2025
      The control is unable to read the Boiler Supply Sensor 082 on terminals 8 and 9 because of a short circuit. Check the boiler supply sensor wire for short circuits according to the sensor installation manual. You might need to replace the boiler supply sensor.
  • T
    Timothy AcevedoSep 1, 2025
    What does 'BOILER SUPPLY SENSOR OPEN CIRCUIT ERROR' mean on my Tekmar 680?
    • J
      Jason LivingstonSep 1, 2025
      This error indicates that the control is unable to read the Boiler Supply Sensor 082 on terminals 8 and 9 due to an open circuit. Check the boiler supply sensor wire for open circuits according to the sensor installation manual. If necessary, replace the boiler supply sensor.
  • W
    Wendy DoughertyAug 31, 2025
    How do I address a 'SYSTEM RETURN SENSOR SHORT CIRCUIT ERROR' on my Tekmar 680?
    • K
      Kaitlyn KruegerAug 31, 2025
      The control is unable to read the System Return Sensor 082 on terminals 11 and 13 because of a short circuit. Check the system return sensor wire for short circuits according to the sensor installation manual. It may be necessary to replace the system return sensor.
  • M
    Meghan GriffithAug 30, 2025
    What causes 'SYSTEM RETURN SENSOR OPEN CIRCUIT ERROR' on Tekmar 680?
    • R
      Rebecca BowmanAug 30, 2025
      This error means that the control cannot read the System Return Sensor 082 on terminals 11 and 13 due to an open circuit. You should check the system return sensor wire for open circuits as described in the sensor installation manual. If needed, replace the system return sensor.
  • A
    anthony52Aug 29, 2025
    How to fix 'SYSTEM SUPPLY SENSOR SHORT CIRCUIT ERROR' in Tekmar 680?
    • A
      Ashley BrownAug 29, 2025
      The control is unable to read the System Supply Sensor 082 on terminals 11 and 12 because of a short circuit. Check the system supply sensor wire for short circuits according to the sensor installation manual. Replacing the system supply sensor may be necessary.
  • W
    William RogersAug 28, 2025
    How to resolve a 'SYSTEM SUPPLY SENSOR OPEN CIRCUIT ERROR' on Tekmar 680?
    • K
      Kevin DuranAug 28, 2025
      The control can't read the System Supply Sensor 082 on terminals 11 and 12 because of an open circuit. Check the system supply sensor wire for open circuits according to the sensor installation manual. It might be necessary to replace the system supply sensor.
  • D
    Derek HarringtonAug 27, 2025
    How do I troubleshoot a 'OUTDOOR SENSOR SHORT CIRCUIT ERROR' on my Tekmar 680 Melting Machines?
    • R
      Randall ShepherdAug 28, 2025
      The control is unable to read the Outdoor Sensor 070 on terminals 14 and 15 because of a short circuit. Check the outdoor sensor wire for short circuits as described in the sensor installation manual. You might need to replace the outdoor sensor.
  • D
    Dr. Laura MaysAug 27, 2025
    How to fix a 'OUTDOOR SENSOR OPEN CIRCUIT ERROR' on Tekmar Melting Machines?
    • L
      Lisa GregoryAug 27, 2025
      The control cannot read the Outdoor Sensor 070 on terminals 14 and 15 because of an open circuit. Check the outdoor sensor wire for open circuits according to the sensor installation manual. Replacing the outdoor sensor might be required.

Summary

Introduction and Features

System Overview

Details the purpose and capabilities of the Snow Melting Control 680.

Key Features

Lists the main functionalities and communication protocols supported by the control.

Getting Started

Initial Setup Guidance

Provides an introduction to the manual's content for installation, programming, and testing.

Safety and Installation Procedures

Safety Warnings and Compliance

Covers essential safety alerts, electrical hazards, and RF interference guidelines.

Installation Preparation and Location

Details tools, materials, packaging, and optimal placement for the control unit.

Wiring the System

Explains sensor, communication, control, boiler, pump, and power wiring connections.

Testing, Overrides, and Settings

Guides on testing sensor/control wiring, manual overrides, and switch settings.

User Interface and System Operation

Interface Navigation and Screens

Describes the home screen, menus, status screens, and symbols used on the control.

System Status and Monitoring

Details available status information for slab, system, boiler, and sensors.

Sequence of Operation

Explains how the control operates in different modes like Melt, Idle, Storm, and Off.

Application Modes Explained

Covers electric, PWM zone, boiler, mixing, and combined operating modes.

Troubleshooting and Technical Data

Troubleshooting Error Messages

Lists common error codes and their corrective actions for system issues.

Frequently Asked Questions

Provides solutions to common symptoms and operational queries.

Technical Specifications

Lists detailed electrical, physical, and environmental data for the control.

Warranty and Returns

Outlines the terms of the limited warranty and product return procedure.

Tekmar 680 Specifications

General IconGeneral
BrandTekmar
Model680
CategoryMelting Machines
LanguageEnglish