© 2007 D 161 - 08/07 12 of 36
Mode Item Field Range Access Description
2
50 to 104°F
(10.0 to 40.0°C)
Default = 104°F
(40.0°C)
ADV
HOT TUB MAXIMUM
SECTION B
Select the maximum hot tub temperature range
adjustment.
3
50 to 200°F
(10 to 93.5°C)
Default = 140°F
(60.0°C)
ADV
DHW MAXIMUM SECTION C
Select the maximum domestic hot water tank temperature
range adjustment.
4
50 to 110°F
(10.0 to 43.5°C)
Default = 85°F
(29.5°C)
ADV
FLOOR MAXIMUM SECTION D
Select the maximum floor temperature range
adjustment.
1
2
3
1 to 40°F
(0.5 to 22.0°C)
Default = 10°F
(5.5°C)
InST
ADV
DIFFERENTIAL
Select the differential to cycle on and off around the setpoint
temperature.
ADJUST Menu (3 of 5)
ADJUST MENU
Continued on next page.