Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
62
T1
START
ADDRESS
5010
OPERATION
510 + 01
TEXT MENU
7. SCHEDULES 1. TIMESLOTS 1. TIMESLOT 1. START
Start time for arming on Timeslot 1
The start time of Timeslot 1 is set at this address. The start time must be less than the stop time set
at address 5011. The engineer sets the start time in format [HH:MM].
Default setting: [00:00]
T1
END
ADDRESS
5011
OPERATION
511 + 01
TEXT MENU
7. SCHEDULES 1. TIMESLOTS 1. TIMESLOT 2.END
End time for disarming on Timeslot 1
The stop time of Timeslot 1 is set at this address. The stop time must be greater than the start time
set at address 5010. The engineer sets the stop time in format [HH:MM].
If a user code has been set a timeslot from 8:30 to 17:00h, the respective user can use his code
within that specified time. From 17:00 to 0:00h and from 0:00 to 8:30h the respective code will
remain inactive.
Default setting: [00:00]
T1
DAYS
ADDRESS
5012
OPERATION
512 + 01
TEXT MENU
7. SCHEDULES 1. TIMESLOTS 1. TIMESLOT 3.WEEK DAYS
Setting of week days for operation on Timeslot 1
The days of the week during which the timeslot 1 is to be used are set at this address.
The days of the week are selected with the digits buttons from 1 to 7. The selected days are
presented with a digit on the display or lighting on LED number see the table below for
correspondence:
Button
Week day
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
For example, if only Wednesday is set for the timeslot, the user code will only be valid on
Wednesday from 8:30 to 17:00h.
Default setting: none