Eclipse 8/16/32/99 Series - Installation Manual
16
2.3.4 Connecting Fire Lines
Fire detectors can be connected to every zone set as Fire type zone.
For ECLIPSE 8 and ECLIPSE 16 is possible to realize only 4-wire connection of 12V alarm fire base with one or two
balancing resistors.
For ECLIPSE 32 and ECLIPSE 99 is possible to realize 4-wire connection of 12V alarm fire base with one or two
balancing resistors and also connection of two fire detectors to a doubling zone.
PGM 4 for ECLIPSE 32 and ECLIPSE 99 has a special functionality. The output can be programmed to operate as Fire
zone with realizing of 2-wire connection of standard 24V fire alarm base.
A) Connecting a fire detector with one balancing
resistor
The PGM 1 must be programmed as Fire Reset
and the active status must be +12V.
The PGM 1 Fire reset option for activation is
programmed at address 3013 event 61.
The Zone type is programmed at address 2xx1,
where “xx” is the zone number.
B) Connecting a fire detector with two balancing
resistors
The PGM 1 must be programmed as Fire Reset
and the active status must be +12V.
The PGM 1 Fire reset option for activation is
programmed at address 3013 event 61.
The Zone type is programmed at address 2xx1,
where “xx” is the zone number.
C) Connecting of two fire alarm detectors to a
zone with set doubling connection style
The PGM 1 must be programmed as Fire Reset
and the active status must be +12V.
The PGM 1 Fire reset option for activation is
programmed at address 3013 event 61.
The Zone type is programmed at address 2xx1,
where “xx” is the zone number.
* Note: Instead of 1k resistor, you can use also
two 510Ohm resistors (by one for every fire
detector), instead one 1K resistor.
D) Realization of 2-wire connection of standard
fire bases to PGM 4 programmed as Fire Zone
at address 3000 in the menus of ECLIPSE32/99
control panel.
Figure 12. Connecting of Fire detectors
Fire
detector
base
Fire
detector
base
Fire
detector
base 1
Fire
detector
base 2
*
ECLIPSE
8/16/32/99
ECLIPSE
8/16/32/99
ECLIPSE 32/99