Eclipse 8/16/32/99 Series - Installation Manual
37
8. APPENDIX – Quick Guide of the Engineer Programming Menus
Review the memory log of the system.
Perform test for operation of all devices in the system.
Perform test of the operation of the PGM outputs in the system.
Perform test of the operation of the built-in digital communicator.
Review the software version of the panel.
Enter time in range 010-180 seconds. Default: 010
Enter time in range 000-254 minutes. Default: 030
Perform a reset for a selected menu. Confirm with code 123456.
Returns to default parameters of all general settings in the system.
Returns to default parameters and access codes of Users.
Returns to default parameters and operation of Inputs and Zones.
Returns to default parameters and operation of PGM outputs.
Returns to default parameters and operation of Areas.
Return to defaults for Time Slots.
Returns to default parameters and operation of all communication devices.
Deletes all devices connected to the system bus, except the PCB of the panel.
Perform a reset of the Manager code. Default: 0000 Confirm with 123456.
Enter a unique name for the system. The menu is accessible via LCD keyboard.
Select the type of the programming menus:
4-digit Addresses [1], 3-digit operations [2], Text [3]
Programming of user rights and options; XX - user number; Y - option number.
1.Disarm/2.Part. Arm/3.Zone Bypass/
4.Programming
1.Disarm/2.Part. Arm/3.Zone Bypass/
4.Programming/8.Manager
Enter a unique name for the User. The menu is accessible via LCD keyboard.
1. Disarm/2+3.Proxy card arming options
0.Unused/1.Sleep Arm/2.Stay Arm/3.Fire Alarm/
4.Medical Alarm/5.Police Alarm
Change the Engineer code. Default: 7777. To change – press and hold “0”.
[4/6] – length of the access codes
Copying user options from one to more.
Set connection style 1-5. Default: 2.
Set connection style 1-9. Default: 2.
Set number 1-9. Default: 6.
Number of activations 2-9. Default: 0 (Disabled).
Time for zones in pulse count: 000-255 sec. Default: 000 sec.
Programming of zone options; XX - zone number; Y - option number.
[DD] [TT] – DD: device number; TT: terminal number
00.Unused/01.Entry-Exit/02.Follow/03.Instant/04.Fire/05.Panic/
06.Tamper/07.Medical/08.Key-Switch/09.Auxiliary/10.Entry-Exit 2
2.Bypass/3.Stay Arm/4.Sleep Arm/
5.Force Arm/6.Double Knock
1.AutoBypass/2.Bypass/3.Stay Arm/
4.Sleep Arm/5.Force Arm/6.Double
Knock/7.Instant Exit/8.Fast (64ms)