EasyManua.ls Logo

TELEVAC MM200 - Set Point Setting Values

TELEVAC MM200
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTRUMENT MANUAL
VACUUM GAUGE MODEL MM200
160Phone:(215) 947-2500 fax:(215) 947-7464 e-mail:sales@televac.com web site:www.televac.com
MM-200_im REV M
Page 88 of 160
TELEVAC
SET POINT SETTING VALUES
SENSOR UNITS RANGE SETTING
1E TORR 1-1000 0001H to 0999H
1F TORR 0.1e3 to 9.9e3 0010 to 0990
2A MICRONS 0-1000 0001L to 0999L
TORR 1.0-20.0 0010H to 0200H
3D,3E,7F TORR 0.0e-11 to 9.9e-2 0.0-B to 9.9-2
4A MICRONS 1-1000 0001L to 0999L
TORR 1-1000 0001H to 0999H
7B TORR 1e-6 to 1.0e-3 0001L to 0990L
7E TORR 1.0e-8 to 9.9e-6 0001L to 0990L
TORR 1.0e-5 to 9.9e-3 0001H to 0990H
008000 (not used)
010000 Sensor #1 zero out of range
020000 Sensor #2 zero out of range
040000 Sensor #3 zero out of range
080000 Sensor #4 zero out of range
100000 Sensor #5 zero out of range
200000 Sensor #6 zero out of range
400000 Sensor #7 zero out of range
800000 Sensor #8 zero out of range
"RY<cr>" 5. Send relay status. The response to this command is two characters followed
by a <cr>. The first character corresponds to relay board #2 (PCR2). The
second corresponds to relay board #1 (PCR1). If either board is not installed
a lower cans "n" is sent for it's character, otherwise and ASCII character is
sent. The character is interpreted as a hex value where each of the bits is a
"one" if the corresponding relay is energized, or a "zero" otherwise. For
example: a response of "nC<cr>" would indicate that relay module number
two (2) is not installed, and that relays #3 and #4 are operated. "C" hex =
1100.
"ST<cr>"
6. The status command. The "ST<cr>" command provides a quick look at the
status of the modular unit. An example of using this command is:

Table of Contents