EcoInsight I, O & M Guide
Telkonet, Inc.
For Use with Firmware Version 2.x
20800 Swenson Drive, Suite 175
Low Voltage Installation
Waukesha, WI 53186
Revision 4.2
(414) 302-2299
Page 25
www.telkonet.com
Resistance/Temperature curve = "J"
Beta ( 0 to 50 degrees C ) = 3892 degrees K nominal
Other models may be compatible; provide model number and specifications.
Analog Outputs
(SS6000-VO model only)
The Analog outputs can be used to control multiple functions. The desired function must be specified at the time of
programming.
1. Fan Coils Variable Valve Control 0-10 or 4-20mA (Both Heat & Cool)
2. ECM Fan motor variable control between speeds. (0-10VDC)
CT Inputs
All Models have 1 input; SS6000-CT has an additional 2 CT inputs for a total of 3. The CT Inputs are commonly used
for monitoring/alerting on fan motors, compressors or other equipment with excessive load or for determining a failure.
The CT Inputs must be used with a compatible CT and sized appropriately for the load they will be connected to.
Current Transformer (CT) approved models from Sentran Corp.:
Rated loads are 100, 50, 30, 20 and 10 A respectively.
BCF-100A: 0.025A
LCF-50A: 0.025A
LCF-30A:0.025A
LCF-20A:0.025A
LCF-10A: 0.01A
Preferred operating range is between 10 and 80% of rated load.
Other models may be compatible: provide model number and specifications
If not sized correctly the CT may damage the thermostat.
J8 Connector
The J8 Connector provides access to 2 Dry Contact Inputs. The Dry Contact Inputs can be configured for a variety of
options. Determine the desired function prior to final programming.
Dry Contact Options:
1. Entry Door Occupancy Assist
2. Lanai Door HVAC disable
3 Housekeeping Status
4. DND Status
5. HVAC Alarm
6. AquaStat
7. Key Card
8. 3rd Party Occupancy Sensor