EasyManua.ls Logo

Telkonet Ecosmart EcoInsight - Calibrate the Analog Output to 5.0 V

Telkonet Ecosmart EcoInsight
44 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EcoInsight I, O & M Guide
Telkonet, Inc.
For Use with Firmware Version 2.x
20800 Swenson Drive, Suite 175
Appendix A
Waukesha, WI 53186
Revision 4.2
(414) 302-2299
Page 43 www.telkonet.com
Calibrate the Analog Output to 5.0V
Equipment Needed: Voltmeter
Set voltmeter to DC Voltage.
On J5, measure between Pin 1 (Orange) and Pin 5 (White).
Change thermostat mode to OFF.
Enter Advanced Command 35 01 and press ON/OFF.
Enter Advanced Command 36 36 and press ON/OFF.
This should cause your reading to go close to 5.0V.
Change the value of 36 36 up or down a few values so it reads close to 5.0V. If you have to raise it
more than 36 70 or lower than 36 50, then there is an issue. Contact engineering
Enter Advanced Command 35 00
Verify that in the OFF mode, output is approx 0.0V.