EcoTouch+ IO&M Guide
Telkonet, Inc.
For Use with Firmware Version 2.x
20800 Swenson Drive, Suite 175
Waukesha, WI 53186
Revision 5
(414) 302-2299
Page 20
www.telkonet.com
If Commissioning Test Fails
a
b
c
a
b
c
Occupancy FAIL
PIR detected too much movement.
1. Verify no one entered the room during commissioning.
2. If no one entered, it is likely the sensor detected too much air movement. This usually requires
that you relocate the EcoTouch to a better place in the room, away from blowing air.*
3. Once moved, test again (touch Retest).
-> The message next to “FAIL” indicates which mode/speed the HVAC was in when the failure occurred.
Cool FAIL
HVAC Cool mode is not operating properly.
1. Look at the message displaying which mode and/or fan speed is malfunctioning.
2. Repair the HVAC malfunction.
3. Run commissioning test again (touch Retest).
Heat N/A or FAIL
“N/A”: HVAC system does not have a heat mode.
“FAIL”: HVAC Cool mode is not operating properly.
1. Look at the message displaying which mode and/or fan speed is malfunctioning.
2. Repair the HVAC malfunction.
3. Run commissioning test again (touch Retest).