EasyManua.ls Logo

Tense EM-07K - Setup Settings; Current Transformer Ratio; Current Transformer Cable Turn Number; Demand Time

Tense EM-07K
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.1 - Setup Settings:
-7-
Pr.1: Current Transformer Ratio
Pr.2: Voltage Transformer Ratio
Pr.3: Current Transformer Cable Turn Number
Pr.4: Demands Time
Pr.5: Demand Record Delete
Pr.6: Energy Record Delete
Figure-36Figure-35
Set
Esc
Press Menu button and enter password (Default Password =0000) to enter program list. The figure-31 is
displayed when you enter password and press the Menu button. You enter setup menu when you press
Menu button. If you enter setup menu, the figure-35 displayed. This menu have 6 different parameters.
When you press the up button to see the other set values on the display, the next data is displayed.
The figure-35 is displayed when you press the up button after the Pr.6 is displayed. By using up-down
buttons select the program. Press Menu to enter required program. By up-down buttons, you can set the
program. Press Menu to record your settings, if you press ESC button, you cannot record your settings.
Figure-31
Figure-38
Figure-37
Figure-39Figure-40
Figure-35
Figure-36
Figure-37
Figure-38
Figure-39
Figure-40
Pr.1: Current Transformer Ratio: If a current transformer which has a ratio of
100/5A is used between the system and device; Current transformer ratio is entered
as = 100/5 = 20. If the current transformer is not used between the system and device,
current transformer ratio is entered as ”1”
Default: 1, Min: 1, Max: 2000
Pr.2: Voltage Transformer Ratio: If you use medium voltage , you can use VTR
Default: 1, Min: 1, Max: 999
Pr.3: Current Transformer Cable Turn Number: User defines the turn number, which
is the number of how much tour the current cable has rounded into the current
transformer. Numbers can be selected between 1-20. Greater the number of turn means
greater the sensitivity
Default: 1, Min: 1, Max: 20.
Pr.4: Demand Time: Determines demand calculate time. Demand is calculated using
average value. Device take sample for demand time and calculate average value.
Demand is maximum average value.
Default: 15min, Min: 1min, Max: 120min.
Pr.5: Demand Record Delete: You can delete demand and average records.
Pr.6: Energy Record Delete: You can delete energy records.

Related product manuals