EasyManua.ls Logo

Tescom Prime Plus Series - Faults Reference Code; Warning Indicator

Tescom Prime Plus Series
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
65
USER MANUAL
PRIME PLUS 1/1 1-3 kVA ΟNLINE UPS
27
3-7. Faults Reference Code
Fault event
Fault code
Icon
Fault event
Fault code
Icon
Bus start fail
01
x
Battery voltage too high
27
x
Bus over
02
x
Battery voltage too low
28
x
Bus under
03
x
Charger output short
2A
x
Inverter soft start fail
11
x
Over temperature
41
x
Inverter voltage high
12
x
Overload
43
Inverter voltage Low
13
x
Charger failure
45
x
Inverter output short
14
x
Over input current
49
x
3-8. Warning indicator
Warning Icon (flashing) Code Alarm
Low Battery
Sounding every 2 seconds
Overload
Sounding every second
Over input current
Sounding 2 beep every 10 seconds
Battery is not connected
Sounding every 2 seconds
Over Charge
Sounding every 2 seconds
Site wiring fault
Sounding every 2 seconds
EPO enable
Sounding every 2 seconds
Over temperature
Sounding every 2 seconds
Charger failure
Sounding every 2 seconds
Battery fault
Sounding every 2 seconds
(At this time, UPS is off to remind
users something wrong with battery)
Out of bypass voltage range
Sounding every 2 seconds
Bypass frequency unstable
Sounding every 2 seconds
Battery replacement
Sounding every 2 seconds
EEPROM error
Sounding every 2 seconds
NOTE: Site Wiring Fault function can be enabled/disabled via software. Please check
software manual for the details.

Table of Contents