PRIME PLUS � 1/1 � 1-3 kVA � ΟNLINE UPS
Symptom Possible cause Remedy
Fault code is shown as 14 on LCD
display and alarm is continuously
sounding.
automatically because
short circuit occurs on the
UPS output.
Check output wiring and if
connected devices are in
short circuit status.
Fault code is shown as 01, 02, 03,
11, 12, 13 and 41 on LCD display
and alarm is continuously
sounding.
A UPS internal fault has
occurred. There are two
possible results:
1. The load is still supplied,
but directly from AC power
via bypass.
2. The load is no longer
supplied by power.
Battery backup time is shorter
than nominal value.
charged
Charge the batteries for at
least 5 hours and then
check capacity. If the
problem still persists,
replace the battery.
Fault code is shown as 2A on LCD
display and alarm is continuously
The short circuit occurs on
the charger output.
Check if battery wiring of
connected external pack is
Fault code is shown as 45 on LCD
display. At the same time, alarm is
The charger does not have
output and battery voltage
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years
at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours
Be sure to deliver the spent battery to a recycling facility or ship it to your
dealer in the replacement battery packing material.