Table 3. Least Common, but Supported Installation Option
Wiring Configuration Option for Four Wires: Line 1, Line 2, Neutral, PE
*When connecting to a 230 V delta no
neutral grid, land one of the line
connections in the neutral terminal of
the wirebox.
Grid type options:
Delta 230 V Line to Line
Open wye with 230 V Line
to Neutral
Split phase 230 V Line to
Neutral
NOTE: In the case of a Delta grid
connection, land one of the line
conductors from the grid in the
neutral terminal of Wall Connector
wirebox.
NOTE: The conductor with lowest
voltage to Protective Earth (PE)
should be connected to the
Neutral terminal.
CAUTION: Double check N
connection is 230 V L to N at
terminals of wirebox before
energizing.
POWER SUPPLY OPTIONS
8Gen 3 Wall Connector Manual