EasyManua.ls Logo

TESVOLT TS 48V - 6.4 E-STOP CONTACT

TESVOLT TS 48V
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INsTAllATION 35
© TESVOLT We reser ve the right to make technical changes. Version RD.TI.015.E.ENG_Installation_Manual_TS48V_v.C.01 Last revised 06/2020
22
Only connect the DC cables
5.1
/
5.2
to the APU LV once the
SMA Sunny Island is completely connected. Fasten the DC con-
necting cable with red marking
5.1
to the CHARGER “+” connec-
tion
1
and the DC connecting cable with blue marking
5.2
to the
CHARGER “–” connection
2
. Use two M8 self-locking nuts
3.5
to
fasten, and tighten to a torque of 12 Nm.
Finally, fix the DC cables in the cable retention clips
F
.
23
Connect the CAN SMA connection
7
on the APU LV to the Com-
Sync IN connection on the SMA Sunny Island using a patch cable
5.3
.
24
Then connect the LAN connection
8
on the APU LV and the ComETH connection on the
SMA Sunny Island using the switch.
25
Finally, fill out the commissioning protocol. You will find a template for this on the TESVOLT USB-Stick
8
.
. ESTOP CONTACT
The TS 48 V has a quick shutdown (e-stop) function. The unit has a Wago 734-162 two-pin plug that is
accessible from the outside for this purpose. This electrical connection can be connected to an external
control system using the matching Wago 734-102 socket. If necessary, the external control system can
switch off the unit as quickly as possible using a separate (i.e. completely independent) switching path.
The shutdown is much faster than the normal shutdown process. The wiring connection may only be
implemented using a floating contact.
WARNING! Possible damage to the unit due to use of the e-stop.
The e-stop contact is used to quickly shut down the system. As the battery storage system is not
switched off properly when the e-stop is used, damage to the TS 48 V can occur. For this reason, never
use the e-stop to switch off the unit under normal circumstances.
WARNING! Possible damage to the APU or external components due to an unsuitable switching
device.
Connecting a non-floating switching device can result in damage to the APU and/or external compo-
nents.
E-stop states
1. Contacts 1 and 2 of the Wago plug are connected, e.g. by an external relay; the e-stop is inactive
and the APU LV is thus switched on.
2. Contacts 1 and 2 on the Wago plug are open, e.g. after activation of the external switch; the e-stop
is active (this is shown on the APU LV display); the DC connection between the TS 48 V and the
SMA Sunny Island is interrupted.
STOP
STOP

Table of Contents