MANUAL: TORNADO
& TORNADO RC MONITOR
Read instruction manual before use. Operation of this device without
understanding the manual and receiving proper training is a misuse of this
equipment. A person who has not read and understood all operating and safety
instructions is not qualified to operate the Tornado or Tornado RC Monitor.
DANGER
Maximum Recommended Flow
is 500 gpm (1900 l/min)
Maximum Recommended Pressure
is 200 psi (14 bar)
TORNADO RC
TM
TORNADO
TM
LIY-300 May 8, 2007 Rev04
©Copyright Task Force Tips, Inc. 2005-2007
INSTRUCTIONS FOR INSTALLATION, SAFE OPERATION AND MAINTENANCE
®

Table of Contents

Other manuals for TFT Tornado RC

Questions and Answers

  • J
    Jessica BakerSep 10, 2025
    Why won't my TFT Monitor operate from the Y4E-COMM communication interface box or Ladder/Platform version electronics enclosure?
    • R
      Rachel TerrySep 10, 2025
      If your TFT Monitor will not operate from the Y4E-COMM communication interface box or Ladder/Platform version electronics enclosure, it could be due to incorrect wiring. Check the blue & white communication wiring. Another possibility is an incorrect INPUTS configuration. Verify that DIP switch #4 setting matches the system wiring (ON for voltage inputs, OFF for ground inputs).
  • J
    Jill RileyAug 23, 2025
    What to do if the TFT Monitor power LED is not on?
    • K
      Kathleen StewartAug 23, 2025
      If the power LED on your TFT Monitor is not lit, it could be due to reversed polarity. Check the wiring and reverse the polarity to correct this issue.
  • P
    Peter WhiteAug 25, 2025
    Why TFT Monitor power LED is on, but there is no operation?
    • S
      Samantha GrantAug 25, 2025
      If your TFT Monitor's power LED is on but the unit isn't operating, it may be due to low voltage caused by a wire gauge that is too small, a wire length that is too long, a poor connection, or an inadequate apparatus electrical system. Check the connections and wiring according to section 5.
  • S
    Sierra ArmstrongAug 26, 2025
    What causes one axis to fail on my TFT Monitor from any control station?
    • S
      sallenAug 27, 2025
      If one axis on your TFT Monitor fails to operate from any control station, it could be due to several reasons: a loose motor wiring connection (check the axis motor connection), a bad motor control board (interchange motor control boards to see if the problem persists; if not, replace the motor control board), a bad motor (interchange motor control boards; if the problem persists, replace the motor), or a bad membrane switch (replace the membrane switch/operator station).
  • R
    Ralph AriasAug 27, 2025
    How to fix elevation binding on a TFT Monitor?
    • R
      Rachel ThomasAug 27, 2025
      Elevation binding in your TFT Monitor can be caused by debris or damage to the elevation drive parts. Clean out any debris or replace the damaged parts. Also, a lack of lubricant can cause this issue, so grease the parts, referring to section 8.1.
  • R
    Roberta Jones DVMAug 29, 2025
    Why is there horizontal rotation binding on my TFT Monitor?
    • J
      Joshua MontgomeryAug 29, 2025
      Horizontal rotation binding in your TFT Monitor can occur due to debris or damage to the horizontal drive parts. Clean out any debris or replace any damaged parts. Another possible cause is a lack of lubricant, so grease the parts, referring to section 8.1.
  • T
    Thomas SandersSep 18, 2025
    How to fix elevation binding on my TFT Tornado RC Firefighting Equipment?
    • K
      Kelsey ThompsonSep 18, 2025
      Elevation binding in your TFT Firefighting Equipment can be caused by: * Debris or damage to elevation drive parts. Clean out any debris or replace any damaged parts. * Lack of lubricant. Grease the equipment to resolve this.
  • E
    Emily HowardSep 12, 2025
    Why my TFT Monitor operates only from the monitor control station?
    • J
      Janet MoralesSep 12, 2025
      If your TFT Monitor operates only from the monitor control station, the communication board code version may be incompatible. Verify the code versions on the monitor and all operator stations.
  • T
    Terri BallSep 8, 2025
    What should I do if my TFT Monitor will not operate from any station and the STOW & OSC LEDs on the monitor are on solid?
    • C
      Cynthia MccannSep 8, 2025
      If your TFT Monitor will not operate from any station and the STOW & OSC LEDs on the monitor are solid, it is likely due to a bad communication board. Replace the communication board in the monitor.
  • N
    nanthonySep 5, 2025
    What to do if TFT Monitor only operates from the monitor operator station and STOW & OSC LEDs on the remote station blink slowly?
    • A
      Andrea ReyesSep 5, 2025
      If your TFT Monitor only operates from the monitor operator station, and the STOW & OSC LEDs on the remote station blink slowly when a button is pressed, it could be due to incorrect wiring. Check the blue/white communication wiring. Alternatively, it could be a bad communication board. Replace the communication board in the monitor. If the problem persists, replace the communication board in the remote operator station.