MANUAL: TORNADO
& TORNADO RC MONITOR
Read instruction manual before use. Operation of this device without
understanding the manual and receiving proper training is a misuse of this
equipment. A person who has not read and understood all operating and safety
instructions is not qualified to operate the Tornado or Tornado RC Monitor.
DANGER
Maximum Recommended Flow
is 500 gpm (1900 l/min)
Maximum Recommended Pressure
is 200 psi (14 bar)
TORNADO RC
TM
TORNADO
TM
LIY-300 May 8, 2007 Rev04
©Copyright Task Force Tips, Inc. 2005-2007
INSTRUCTIONS FOR INSTALLATION, SAFE OPERATION AND MAINTENANCE
®

Table of Contents

Other manuals for TFT Tornado Series

Questions and Answers

  • J
    johnstephensSep 3, 2025
    Why does the vertical/horizontal axis on my TFT Monitor only run for about 5 seconds and then stop?
    • D
      Dennis BoydSep 3, 2025
      If the vertical or horizontal axis on your TFT Monitor only runs for about 5 seconds and then stops, it could be due to a loose encoder wiring connection. Check the axis encoder connection. It could also be a bad motor encoder. Interchange motor control boards to see if the problem persists with the same axis. If it does, replace the motor. Remove the encoder cover and check for a RED light just below the disk. If there is no light, the encoder is bad. Replace the motor.
  • M
    Madeline RobinsonSep 1, 2025
    Why does the vertical/horizontal axis only run in fast speed on my TFT Monitor?
    • J
      juliedunnSep 1, 2025
      If the vertical or horizontal axis on your TFT Monitor only runs in fast speed, it may be due to a loose encoder wiring connection. Check the axis encoder connection. It could also be a bad motor encoder. Interchange motor control boards. Check if the problem persists with the same axis. If yes, replace the motor. Remove the encoder cover and check for a RED light just below the disk. If there is no light, the encoder is bad. Replace the motor.
  • J
    James ThompsonAug 31, 2025
    Why won't the vertical/horizontal axis speed up on my TFT Monitor?
    • D
      diana15Aug 31, 2025
      If the vertical or horizontal axis on your TFT Monitor will not speed up, it could be due to a loose encoder wiring connection (check the axis encoder connection) or a bad motor encoder (interchange motor control boards to see if the problem persists; if it does, replace the motor. Remove the encoder cover and check for a RED light just below the disk; if there's no light, the encoder is bad, so replace the motor).
  • B
    Benjamin DavisAug 29, 2025
    Why is there horizontal rotation binding on my TFT Monitor?
    • W
      whitney58Aug 29, 2025
      Horizontal rotation binding in your TFT Monitor can occur due to debris or damage to the horizontal drive parts. Clean out any debris or replace any damaged parts. Another possible cause is a lack of lubricant, so grease the parts, referring to section 8.1.
  • A
    Ashley LesterAug 27, 2025
    How to fix elevation binding on a TFT Monitor?
    • J
      Julie ObrienAug 27, 2025
      Elevation binding in your TFT Monitor can be caused by debris or damage to the elevation drive parts. Clean out any debris or replace the damaged parts. Also, a lack of lubricant can cause this issue, so grease the parts, referring to section 8.1.
  • M
    Megan BrooksAug 26, 2025
    What causes one axis to fail on my TFT Monitor from any control station?
    • A
      Adam LongAug 26, 2025
      If one axis on your TFT Monitor fails to operate from any control station, it could be due to several reasons: a loose motor wiring connection (check the axis motor connection), a bad motor control board (interchange motor control boards to see if the problem persists; if not, replace the motor control board), a bad motor (interchange motor control boards; if the problem persists, replace the motor), or a bad membrane switch (replace the membrane switch/operator station).
  • J
    Jeremy HarrisAug 25, 2025
    Why TFT Monitor power LED is on, but there is no operation?
    • R
      Ricky SchmidtAug 25, 2025
      If your TFT Monitor's power LED is on but the unit isn't operating, it may be due to low voltage caused by a wire gauge that is too small, a wire length that is too long, a poor connection, or an inadequate apparatus electrical system. Check the connections and wiring according to section 5.
  • A
    Amber RobinsonAug 22, 2025
    What to do if the TFT Monitor power LED is not on?
    • A
      Ashley PorterAug 22, 2025
      If the power LED on your TFT Monitor is not lit, it could be due to reversed polarity. Check the wiring and reverse the polarity to correct this issue.