The application programmes RAMSES 718 P/S
RAMSES 718 P / RAMSES 718 S 21
4.3.2 Objects for the room temperature controller (RTC)
Object 10: Base set point
RAMSES 718 P: The function of the object is determined using the parameter function of the
rotary control.
Parameter: Rotary
control function
Object function
Base set point
Sends the base set point set at the rotary control.
Manual offset or blocked
Receives the base set point from the bus.
The base set point is first specified via the application at start-up
and stored in the base set point object.
Afterwards, it can be specified again at any time this object (limited
by the minimum or maximum valid set point).
RAMSES 718 S:
Receives the base set point from the bus.
The base set point is first specified via the application at start-up and stored in the base set
point object.
Then it can be re-determined at any time with this object (limited by minimum or maximum
valid target value).
Object 11: Manual set point offset / set point offset at rotary control
6
RAMSES 718 P: The function of the object is determined using the parameter function of the
rotary control
Rotary control
function
Object function
Data
direction
Base set point,
or blocked
Receive manual set point offset.
The object receives a temperature difference.
The desired room temperature (current set point) can be
adjusted against the base set point by this difference.
This applies in comfort mode (heating):
Actual set point = base set point + manual set point offset.
Values outside the configured range are limited to the highest
or lowest value.
If a 0 is received, a set point temperature offset that was
previously entered is reset to 0.
The offset always refers to the set base set point and
not to the current set point.
Receive
Manual offset
Sends the set point offset set at the rotary control.
Send
6
Only RAMSES 718 P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Theben KNX Series and is the answer not in the manual?

Theben KNX Series Specifications

General IconGeneral
Communication ProtocolKNX
Ambient Temperature-5°C to +45°C
Storage Temperature-25°C to +70°C
Protection ClassIP20
Relative Humidity5% to 95%, non-condensing
Operating Voltage24 V DC (via KNX bus)