The application programmes RAMSES 718 P/S
RAMSES 718 P / RAMSES 718 S 39
Designation
Values
Description
Monitor actual value
no
No monitoring.
yes
All selected actual value sources
are monitored.
In case of an error, the object
sends actual value failure error
telegrams.
As long as at least one
valid actual value remains
available, this will be
continued to be used for
control. This is the case if
the average value is
determined out of 2 or 3
sources.
Monitoring time for external
actual value
2 min, 3 min, 5 min,
10 min, 15 min, 20 min,
30 min, 45 min, 60 min
Only for the External actual value
object. If no value is received
within the configured time and
the object is the only selected
source, the emergency program
will be activated.
As long as at least one
valid actual value remains
available, this will be
continued to be used for
control, and the
emergency program
remains inactive. This is
the case if the average
value is determined out of
2 or 3 sources.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Theben KNX Series and is the answer not in the manual?

Theben KNX Series Specifications

General IconGeneral
Communication ProtocolKNX
Ambient Temperature-5°C to +45°C
Storage Temperature-25°C to +70°C
Protection ClassIP20
Relative Humidity5% to 95%, non-condensing
Operating Voltage24 V DC (via KNX bus)