4.6.2 Actual value
On this parameter page the source is selected which is used as the actual value for control. This
can be the temperature sensor integrated in the device, an external sensor, or a combination of
up to 3 sensors.
The control actual value might, depending on the selection of the source for the actual
value, deviate from the internally measured temperature (object temperature value).
13
controls the room temperature
via the internal sensor. (Control
actual value = internally
measured temperature).
object
The room temperature is solely
acquired via the bus.
internal + ext. actual
value object
The device calculates the average
value of the room temperature
received from the bus and the
internal measurement.
internal
+ I3
Average value of the internal
value and the value measured at
I3.
Average value I3
+ Obj. Ext. actual value
Use average value of I3 and bus.
internal
+ I3 + obj. actual ext.
sources: I3 + internal + bus.
Send control actual value in the
event of change of
only cyclical sending possible.
0.2 K, 0.3 K, 0.5 K, 0.7 K
1 K, 1.5 K, 2 K
Minimum change for resending.
Send control actual value
cyclically
Only send in the event of a
change.
Send in the event of a change
and cyclically.
13
The selection possibilities with I3 are only available when the external inputs for temperature
measuremet are set, i.e. function of the external inputs I3 +I4 = temperature sensor input (see