The application programmes RAMSES 718 P/S
RAMSES 718 P / RAMSES 718 S 51
4.6.8 Cooling set points
19
Only in 2 pipe system
20
Only in 2 pipe system
21
Only for type of control heating = 2 points.
22
Only with type of control cooling = 2-point.
Dead zone between heating and
cooling
19
20
2 K, 2.5 K, 3 K, 3.5 K
4 K, 4.5 K, 5 K, 5.5 K, 6 K
+ hysteresis heating
21
+ hysteresis cooling
22
Specifies the buffer zone
between set points for heating
and cooling mode.
The dead zone is expanded
through hysteresis in switching
(2 point) control.
See in the Appendix: Dead zone
(during cooling)
1.5 K, 2 K, 2.5 K
3 K, 3.5 K, 4 K
4.5 K, 5 K
The standby temperature is
increased in cooling mode.
(during cooling)
6 K, 7 K, 8 K
temperature is increased in night
set point for heat protection
mode
(during cooling)
heat protection
29 °C, 30 °C, 31 °C
32 °C, 33 °C, 34 °C
35°C
Heat protection represents the
maximum permitted temperature
for the controlled room. It
performs the same function
during cooling as the frost
protection mode during heating,
e.g. saves energy while
prohibiting non-permitted