EasyManuals Logo

Theben KNX Series User Manual

Theben KNX Series
107 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
The application programmes RAMSES 718 P/S
RAMSES 718 P / RAMSES 718 S 56
4.7.1.1 Switch object parameter pages 1, 2, 3
Each of the 3 objects can be configured individually on its own parameter page.
Designation
Values
Description
Object type
Switching (1 bit)
Priority (2 bit)
Value 0-255
Percentage value (1 byte)
2 byte floating-point number
DPT 9.x
4 byte floating-point number
DPT 14.x
Telegram type for this object.
Send if
input = 1
no
yes
Send if voltage is present at the
input?
Telegram
With object type = switching 1
bit
ON
Send switch-on command
OFF
Send switch-off command
BY
Invert current state (ON-OFF-ON
etc.)
With object type = priority 2 bit
Function
Value
inactive
Priority not active
(no control)
0 (00bin)
ON
Priority ON
Priority ON (control:
enable, on)
3 (11bin)
OFF
Priority OFF
(control: disable, off)
2 (10
bin)
With object type = value 0-255
0-255
Any value between 0 and 255
can be sent.
With object type = percentage
value 1 byte
0-100%
Any percentage value between 0
and 100 % can be sent.
With object type = 2 byte
floating-point number
-670760…670760
Std.: 0
Any value between -670760 and
670760 can be sent.
With object type = 4 byte
floating-point number
-1E+38.. 1E+38
Std.: 0
Any value between -1E+38 and
1E+38 can be sent.
Input format: The ETS only allows
the input as a decimal without
power.
Example: 15234825.123456
Send if
input = 0
no
yes
Send if voltage is present at the
input?
Telegram
See above: Same object type as
Send if input = 1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Theben KNX Series and is the answer not in the manual?

Theben KNX Series Specifications

General IconGeneral
Communication ProtocolKNX
Ambient Temperature-5°C to +45°C
Storage Temperature-25°C to +70°C
Protection ClassIP20
Relative Humidity5% to 95%, non-condensing
Operating Voltage24 V DC (via KNX bus)