EasyManuals Logo

Theben KNX Series User Manual

Theben KNX Series
107 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
The application programmes RAMSES 718 P/S
RAMSES 718 P / RAMSES 718 S 57
Designation
Values
Description
Send cyclically
no
yes, always
only if input = 1
only if input = 0
When should be sent cyclically?
The cycle time is set on the main
parameter page of the channel.
Response after
restoration of the bus
supply
none
Do not send.
update (immediately)
update (after 5 s)
update (after 10 s)
update (after 15 s)
Send update telegram
immediately or with delay.
Response when setting
the block
Ignore block
The block function is ineffective
with this telegram.
no response
Do not respond when setting the
block.
as with input = 1
Respond as with rising edge.
as with input = 0
Respond as with falling edge.
Response when
cancelling the block
no response
Do not respond when the block is
cancelled.
update
Send update telegram.
If a channel is blocked, no telegrams will be sent cyclically.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Theben KNX Series and is the answer not in the manual?

Theben KNX Series Specifications

General IconGeneral
Communication ProtocolKNX
Ambient Temperature-5°C to +45°C
Storage Temperature-25°C to +70°C
Protection ClassIP20
Relative Humidity5% to 95%, non-condensing
Operating Voltage24 V DC (via KNX bus)