Typical applications
RAMSES 718 P / RAMSES 718 S 79
5.2.5 Important parameter settings
Standard or customer-defined parameter settings apply to unlisted parameters.
RAMSES 718 P:
Parameter page
Parameter
Setting
RTC setting
Control
Heating control only
Rotary control function
Manual offset
Button function
Presence button
Operating Mode
Objects for determining the operating
mode
New: Operating mode, presence,
window status
Channel I1
Activate channel
ON
Channel function
Switch
Number of telegrams
One telegram
Switch object 1
Object type
Switching (1 bit)
Send if input = 1
yes
Telegram
ON
Send if input = 0
yes
Telegram
OFF
Send cyclically
yes
Response after restoration of the bus
supply
update (immediately)
TR 648 top2 RC:
Parameter page
Parameter
Setting
General
Activate time switch
channel C1
yes
Switching channel C1
Telegram type C1.1
HVAC operating mode
As with clock -> ON
send following telegram once
Telegram
Standby
With clock -> OFF
send following telegram once
Telegram
Temperature reduction at night
HM 6 T:
Parameter page
Parameter
Setting
Channel H1: Configuration
options
Channel function
Heating actuator
Type of actuating value
continuous..

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Theben KNX Series and is the answer not in the manual?

Theben KNX Series Specifications

General IconGeneral
Communication ProtocolKNX
Ambient Temperature-5°C to +45°C
Storage Temperature-25°C to +70°C
Protection ClassIP20
Relative Humidity5% to 95%, non-condensing
Operating Voltage24 V DC (via KNX bus)