The application programmes RAMSES 718 P/S
RAMSES 718 P / RAMSES 718 S 8
4.2.2 Room temperature controller (RTC)
.
Object name Function Length R W C T DPT
10
Base set point
Defining the set
temperature
2 bytes - W C - 9,001
Base set point at rotary control
4
Send 2 bytes R - C T 9,001
11
Manual set point offset Receive 2 bytes - W C - 9,002
set point offset at rotary control
5
Send 2 bytes R - C T 9,002
12
Outdoor temperature
compensation
Send 2 bytes R - C T 9,001
Adjust set point 2 bytes - W C - 9,002
13
Operating mode preset Receive 1 byte - W C - 20,102
Night <-> standby Receive 1 bit - W C - 1,001
14
Comfort Receive 1 bit - W C - 1,003
Presence Receive 1 bit - W C - 1,018
15
Window status Closed=0, open=1 1 bit - W C - 1,019
Frost Receive 1 bit - W C - 1,003
16 Current operating mode Send 1 byte R - C T 20,102
17 Operating mode as scene
call up
1 byte - W C T 18,001
18 Heating actuating value
Send 1 bit - - C T 1,001
Send 1 byte - - C T 5,001
18 Heating/cooling actuating value
Send 1 bit - - C T 1,001
Send 1 byte - - C T 5,001
19
PWM heating additional stage Send 1 bit - - C T 1,001
Actuating value additional
heating stage
Send 1 byte - - C T 5,001
20 Cooling actuating value
Send 1 bit - - C T 1,001
Send 1 byte - - C T 5,001
21
PWM cooling additional stage Send 1 bit - - C T 1,001
Actuating value additional cooling
stage
Send 1 byte - - C T 5,001
22
Send heating mode/cooling
mode
1 bit R - C T 1,001
1 bit R - C T 1,100
Switching between heating and
cooling
1 bit - W C - 1,001
1 bit - W C - 1,100
23 Current set point Setting/sending 2 bytes - W C T 9,001
24 Control actual value Send 2 bytes R - C T 9,001
25 External actual value Receive 2 bytes - W C - 9,001
4
Only RAMSES 718 P
5
Only RAMSES 718 P