Appendix
RAMSES 718 P / RAMSES 718 S 91
6.4.2 Format of set point correction: Absolute
Sends the corrected set point to the bus for additional room thermostats.
This set point is calculated from:
Base set point without correction + dead zone + adjustment.
Example: set point correction from: 25 °C, start set point: 20 °C, dead zone = 2 K
Outdoor temp.
Adjustment
1 K/1 K
1 K/2 K
1 K/3 K
1 K/4 K
1 K/5 K
1 K/6 K
1 K/7 K
20
22.00
22.00
22.00
22.00
22.00
22.00
22.00
set point
21
22.00
22.00
22.00
22.00
22.00
22.00
22.00
22
22.00
22.00
22.00
22.00
22.00
22.00
22.00
23
22.00
22.00
22.00
22.00
22.00
22.00
22.00
24
22.00
22.00
22.00
22.00
22.00
22.00
22.00
25
23.00
26
24.00
23.00
27
25.00
24.00
23.00
28
26.00
24.00
24.00
23.00
29
27.00
25.00
24.00
24.00
23.00
30
28.00
25.00
24.00
24.00
24.00
23.00
31
29.00
26.00
25.00
24.00
24.00
24.00
23.00
32
30.00
26.00
25.00
24.00
24.00
24.00
24.00
33
31.00
27.00
25.00
25.00
24.00
24.00
24.00
34
32.00
27.00
26.00
25.00
24.00
24.00
24.00
35
33.00
28.00
26.00
25.00
25.00
24.00
24.00
36
34.00
28.00
26.00
25.00
25.00
24.00
24.00
37
35.00
29.00
27.00
26.00
25.00
25.00
24.00
38
36.00
29.00
27.00
26.00
25.00
25.00
24.00
39
37.00
30.00
27.00
26.00
25.00
25.00
25.00
40
38.00
30.00
28.00
26.00
26.00
25.00
25.00

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Theben KNX Series and is the answer not in the manual?

Theben KNX Series Specifications

General IconGeneral
Communication ProtocolKNX
Ambient Temperature-5°C to +45°C
Storage Temperature-25°C to +70°C
Protection ClassIP20
Relative Humidity5% to 95%, non-condensing
Operating Voltage24 V DC (via KNX bus)