39
Table 13 Water Cooled & Remote Air Cooled Condenser Chiller Electrical Data (60 Hz) - continued
Model
Process
Pump
Size
Rated
Voltage
Allowable Power
Supply
Compressor Data
Pump
Data
Unit Data
Comp 1
Comp 2
Min
Max
RLA
1
LRA
2
RLA
1
LRA
2
FLA
3
MCA
4
MOP
5
NQW10
&
NQR10
None
230/3/60
187
253
48.1
245.0
-
-
0.0
62.6
110.7
1.5 HP
230/3/60
187
253
48.1
245.0
-
-
6.0
68.6
116.7
3 HP
230/3/60
187
253
48.1
245.0
-
-
9.6
72.2
120.3
5 HP
230/3/60
187
253
48.1
245.0
-
-
15.2
77.8
125.9
7.5 HP
230/3/60
187
253
48.1
245.0
-
-
22.0
84.6
132.7
None
460/3/60
414
506
18.6
125.0
-
-
0.0
24.4
43.0
1.5 HP
460/3/60
414
506
18.6
125.0
-
-
3.0
27.4
46.0
3 HP
460/3/60
414
506
18.6
125.0
-
-
4.8
29.2
47.8
5 HP
460/3/60
414
506
18.6
125.0
-
-
7.6
32.0
50.6
7.5 HP
460/3/60
414
506
18.6
125.0
-
-
11.0
35.4
54.0
None
575/3/60
518
633
14.7
100.0
-
-
0.0
19.3
34.0
1.5 HP
575/3/60
518
633
14.7
100.0
-
-
2.4
21.7
36.4
3 HP
575/3/60
518
633
14.7
100.0
-
-
3.8
23.2
37.9
5 HP
575/3/60
518
633
14.7
100.0
-
-
6.1
25.4
40.1
7.5 HP
575/3/60
518
633
14.7
100.0
-
-
8.8
28.1
42.8
NQW15
&
NQR15
None
230/3/60
187
253
55.8
340.0
-
-
0.0
72.3
128.1
3 HP
230/3/60
187
253
55.8
340.0
-
-
9.6
81.9
137.7
5 HP
230/3/60
187
253
55.8
340.0
-
-
15.2
87.5
143.3
7.5 HP
230/3/60
187
253
55.8
340.0
-
-
22.0
94.3
150.1
None
460/3/60
414
506
26.9
173.0
-
-
0.0
34.9
61.8
3 HP
460/3/60
414
506
26.9
173.0
-
-
4.8
39.7
66.6
5 HP
460/3/60
414
506
26.9
173.0
-
-
7.6
42.5
69.4
7.5 HP
460/3/60
414
506
26.9
173.0
-
-
11.0
45.9
72.8
None
575/3/60
518
633
23.7
132.0
-
-
0.0
30.6
54.3
3 HP
575/3/60
518
633
23.7
132.0
-
-
3.8
34.4
58.1
5 HP
575/3/60
518
633
23.7
132.0
-
-
6.1
36.7
60.4
7.5 HP
575/3/60
518
633
23.7
132.0
-
-
8.8
39.4
63.1
1
RLA is Rated Load Amps.
2
LRA is Locked Rotor Amps.
3
FLA is Full Load Amps.
4
MCA is Minimum Circuit Amps (for wire sizing), complies with NEC, Section 430-24.
5
MOPD is Maximum Over-current Protection Device, complies with NEC, Section 430-53.