40
Table 13 Water Cooled & Remote Air Cooled Condenser Chiller Electrical Data (60 Hz) - continued
Model
Process
Pump
Size
Rated
Voltage
Allowable Power
Supply
Compressor Data
Pump
Data
Unit Data
Comp 1
Comp 2
Min
Max
RLA
1
LRA
2
RLA
1
LRA
2
FLA
3
MCA
4
MOP
5
NQW20
&
NQR20
None
230/3/60
187
253
33.3
239.0
33.3
239.0
0.0
77.4
110.7
3 HP
230/3/60
187
253
33.3
239.0
33.3
239.0
9.6
87.0
120.3
5 HP
230/3/60
187
253
33.3
239.0
33.3
239.0
15.2
92.6
125.9
7.5 HP
230/3/60
187
253
33.3
239.0
33.3
239.0
22.0
99.4
132.7
10 HP
230/3/60
187
253
33.3
239.0
33.3
239.0
28.0
105.4
138.7
None
460/3/60
414
506
17.9
125.0
17.9
125.0
0.0
41.5
59.4
3 HP
460/3/60
414
506
17.9
125.0
17.9
125.0
4.8
46.3
64.2
5 HP
460/3/60
414
506
17.9
125.0
17.9
125.0
7.6
49.1
67.0
7.5 HP
460/3/60
414
506
17.9
125.0
17.9
125.0
11.0
52.5
70.4
10 HP
460/3/60
414
506
17.9
125.0
17.9
125.0
14.0
55.5
73.4
None
575/3/60
518
633
12.8
80.0
12.8
80.0
0.0
29.8
42.6
3 HP
575/3/60
518
633
12.8
80.0
12.8
80.0
3.8
33.6
46.4
5 HP
575/3/60
518
633
12.8
80.0
12.8
80.0
6.1
35.8
48.6
7.5 HP
575/3/60
518
633
12.8
80.0
12.8
80.0
8.8
38.6
51.4
10 HP
575/3/60
518
633
12.8
80.0
12.8
80.0
11.2
41.0
53.8
NQW25
&
NQR25
None
230/3/60
187
253
51.3
300.0
51.3
300.0
0.0
117.9
169.2
5 HP
230/3/60
187
253
51.3
300.0
51.3
300.0
15.2
133.1
184.4
7.5 HP
230/3/60
187
253
51.3
300.0
51.3
300.0
22.0
139.9
191.2
10 HP
230/3/60
187
253
51.3
300.0
51.3
300.0
28.0
145.9
197.2
None
460/3/60
414
506
23.1
150.0
23.1
150.0
0.0
53.2
76.3
5 HP
460/3/60
414
506
23.1
150.0
23.1
150.0
7.6
60.8
83.9
7.5 HP
460/3/60
414
506
23.1
150.0
23.1
150.0
11.0
64.2
87.3
10 HP
460/3/60
414
506
23.1
150.0
23.1
150.0
14.0
67.2
90.3
None
575/3/60
518
633
19.9
109.0
19.9
109.0
0.0
45.7
65.6
5 HP
575/3/60
518
633
19.9
109.0
19.9
109.0
6.1
51.8
71.7
7.5 HP
575/3/60
518
633
19.9
109.0
19.9
109.0
8.8
54.5
74.4
10 HP
575/3/60
518
633
19.9
109.0
19.9
109.0
11.2
56.9
76.8
1
RLA is Rated Load Amps.
2
LRA is Locked Rotor Amps.
3
FLA is Full Load Amps.
4
MCA is Minimum Circuit Amps (for wire sizing), complies with NEC, Section 430-24.
5
MOPD is Maximum Over-current Protection Device, complies with NEC, Section 430-53.