SETTING AND COMMISSIONING
68
NA011 - Manual - 05 - 2022
IECLP>inv In 0.005 ... 0.999 step = 0.001
1.00 ... 2.00 step = 0.01
tE>inv s 0.02 ... 9.99 step = 0.01
10.0 ... 60.0 step = 0.1
IE>> Element
IE>> Setpoint
IE>>Curve DEFINITE | IEC/BS A | IEC/BS B | IEC/BS C | ANSI/
IEEE MI | ANSI/IEEE VI | ANSI/IEEE EI | I2T
IECLP>> Off | On-Blocking | On-Changing
tECLP>> s 0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
tE>>RES ms 0 ... 1000 step = 10
IE>> Definite
IE>>def IEn 0.005 ... 0.999 step = 0.001
1.00 ... 5.00 step = 0.01
IECLP>>def IEn 0.005 ... 0.999 step = 0.001
1.00 ... 5.00 step = 0.01
tE>>def s 0.03 ... 10.00 step = 0.01
IE>> Inverse
IE>>inv In 0.005 ... 0.999 step = 0.001
1.00 ... 2.00 step = 0.01
IECLP>>inv In 0.005 ... 0.999 step = 0.001
1.00 ... 2.00 step = 0.01
tE>>inv s 0.02 ... 9.99 step = 0.01
10.0 ... 60.0 step = 0.1
Breaker failure
BF Enable Trip I> | Trip I>> | Trip I>>> | Trip IE> | Trip IE>> |
Trip EXT
tBF s 0.10 ... 0.99 step = 0.01
1.00 ... 10.00 step = 0.05
Store
Oscillography
Info
Records stored 0 ... 2 step = 1
Last record 0 ... 2 step = 1
Recorder state Init | Start | Acquire | Trigger | Store | Reset | Off
| Error
Setting
Pre-trigger T 0 ... 63 step = 1
Trigger Manual | General Start | General Trip | IN1 | IN2 |
IN3 | K1 | K2 | K3 | K4 | Auxiliar
Trigger aux Start I> | Start I>> | Start I>>> | Start IE> | Start
IE>> | Trip I> | Trip I>> | Trip I>>> | Trip IE> | Trip
IE>>
Digital channels General Start | General Trip | IN1 | IN2 | IN3 | K1 |
K2 | K3 | K4
Analog channel 1 OFF | iL1 | iL2 | iL3 | iE | measure IL1 | measure IL2
| measure IL3 | measure IE
Analog channel 2 OFF | iL1 | iL2 | iL3 | iE | measure IL1 | measure IL2
| measure IL3 | measure IE
Analog channel 3 OFF | iL1 | iL2 | iL3 | iE | measure IL1 | measure IL2
| measure IL3 | measure IE
Analog channel 4 OFF | iL1 | iL2 | iL3 | iE | measure IL1 | measure IL2
| measure IL3 | measure IE