EasyManua.ls Logo

Thytronic XMR-P 4l+4V - Page 164

Thytronic XMR-P 4l+4V
384 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
164
FUNCTION CHARACTERISTICS
Thermal image (49MG) - Logic diagram of the trip threshold
Starting control set
Starting
control
&
CLP source
MR Enable
CB-State
I
RUN
= 0.1
I
B
Max[I
L1...
I
L3
]
I
RUN
I
L1...
I
L3
Output t
CLP
t
CLP
Max[I
L1...
I
L3
]
I
RUN
Max[I
L1...
I
L3
]
I
RUN
Max[I
L1...
I
L3
]
<
I
RUN
Starting detection
Reset CLP timer
CB State
CB OPEN CB CLOSED CB CLOSEDCB OPEN
t
I
RUN
t
CLP
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK UNBLOCK UNBLOCK
HIGH THRESHOLD/
BLOCK
HIGH THRESHOLD/
BLOCK
+UAUX
-UAUX
Binary input INx
T 0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
0
n.o.
n.c.
INx
t
OFF
Motor restart
Motor restart
Motor restart
LOW TH. LOW TH.
Fun_49MG_Dth.ai
Dth>
&
Dθ
Dth>
Dth>
ONEnable element
TRIPPING MATRIX
(LED+RELAYS)
Dth> Enable
Dth>-L
Dth>-K
DTh> thermal image (49) block diagram
Block1, Block2
T 0
t
DthCLP
DthCLPMode
t
DthCLP
A
B
C
Output t
DthCLP
Starting control set
A = ON - Change setting
B = OFF
C = ON - Element blocking
1
1
A
B
C
A = ON - Change setting
A
B
C
C = ON - Element blocking
A
B
C
B = OFF
Init DTheta
Binary input INx
T 0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
T0
n.o.
n.c.
INx
t
OFF
I
th
K
ST
(
I
th
within CLP)
(
I
th
outside CLP)
I
th
/K
ST
A =“1”
A =“0”
Change
setting
Change
setting
Element
blocking
B or C
dDθ/dt + Dθ/T+ = (Ith/I
B
)
2
/T+
dDθ/dt + Dθ/T- = 0
T
+
T
-
DthIN
I
th
= √
I
1
2
+K
2
I
2
2
K
2
I
1
I
2
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021

Table of Contents

Related product manuals