EasyManua.ls Logo

Thytronic XMR-P 4l+4V - Control and Monitoring; Synchrocheck - 25

Thytronic XMR-P 4l+4V
384 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
334
FUNCTION CHARACTERISTICS
4.5 CONTROL AND MONITORING
Synchrocheck - 25
Preface
The protection is available in the XMR-V, XMR-P and XMR-G versions.
The synchrocheck function verifies that the connection between two sections of a power system
can take place without endangering the stability of the power system. Typical applications are:
the synchronization of an incoming power supply and a bus-bar, eg. the connection of a line powe-
red by a generator (cogeneration) and bus-bars fed by the Distributor:
synchro check of two busbars via bus coupler.
Inputs
The two grid measured voltages are employed:
V
1
: reference input (three-phases or one-phase); by means of the Synchrocheckvoltageme-
asureV1 parameter (phase-to-phase voltage U
12
or phase-to-neutral voltage U
L1
, available inside
the Set \ Base menu the voltage input can be selected.
1
V
2
: one phase input voltage to be synchronized. Input is used normally used for measuring the re-
sidual voltage (B9-B10 terminals); by means of the
VoltagemeasureUEorV2 parameter (U
E
or
V
2
), available inside the Set \ Base menu, the voltage input can be selected.
[1]
Being the native input unavailable, the residual voltage can be calculated by vector sum from the
three phase voltages.
If a power transformer between the two voltage measurement inputs exists (eg Fig.1), a sw adapta-
tion which allows to compensate the connection group is available without the need of interposing
external adapters; the phase compensation can be carried out by means of the parameter
V1-V2
Phasecorrection, available inside the Set \ Base menu.
[1]
Output relays
The synchrocheck function can activate one or more relays according to the usual allocation matrix
criterion .
The pulse operating mode must be select (Set \ Board 1 outputs menu) and the pulse width must be
set according to the circuit breaker requirements.
Operating mode
The following three operating modes can be select:
0 - Synchro check between two live sections of the plant (synchronous or asynchronous),
1 - Synchro check between live busbars and dead line,
2 - Synchro check between live line and dead busbars.
Note 1 To change the parameter, you must operate at Level 1
BUSBAR
SYNC command
FEEDER
Fig. 1 - Infeed synchronisation
V
2
(one-phase input)
V
1
(three-phase input)
25
PROTECTION RELAY
XMR
BUSBAR 1
BUSBAR 2
Fig.2 - Busbar synchronization
25
Close command
XMR
V
2
V
1
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021

Table of Contents

Related product manuals