Congurable Item B models BC & BE models BAR
SUMMERboost®
Enable Enable Enable
Duct Heater Enable/
Disable
Disable Enabled Enabled
Duct Heater
Frost Frost Frost
Hyst
1 °C 1 °C 1 °C
Duct Heater threshold
4 °C 4 °C 4 °C
Room Sensor 1
Set point Low
0060 0060 0060
Set point High
0070 0070 0070
Room Sensor 2
Set point Low
0800 0800 0800
Set point High
1400 1400 1400
Internal Humidity
Boost
O On On
%RH Boost Set point
70 % 70 % 70 %
%RH Boost Overrun
timer
15 mins 15 mins 15 mins
%RH Boost Hysterisis
1 % 1 % 1 %
Frost set point
2 °C 2 °C 2 °C
Frost Protection Mode
O O O
Room Sensor 1
Enable/Disable
Disable Disable Disable
Room Sensor Type
%RH %RH %RH
Sensor Min Point 0V
0020 0020 0020
Sensor Max Point 10V
0090 0090 0090
Room Sensor 2
Enable/Disable
Disable Disable Disable
Room Sensor Type
CO₂ CO₂ CO₂
Sensor Min Point 0V
0450 0450 0450
Sensor Max Ponit 10V
1850 1850 1850
Switch Input 1
Kitchen Kitchen Kitchen
Switch Input 2
Wet Room Wet Room Wet Room
Switch Input 3
SUMMERboost® SUMMERboost® SUMMERboost®
Live Switch 1 (LS1)
Kitchen Kitchen Kitchen
Live Switch 2 (LS2)
Wet Room Wet Room Wet Room
If the BC or BE models are factory reset via the aurastat V or aurastst VT user non congurable settings and default settings
(above) will revert to the B model values; The unit will require reprogramming by the manufacturer to the correct BC & BE
settings to maintain correct function as Cold Climate units.
27