Commissioning Units TPxxxB/BC/BE/BAR
HRV Controller Options
Once installation of the ducting and HRV is complete the ventilation system will need to be commissioned and setup using
a compatible Titon display interface unit
The Titon display interface units are:
aurastat V*
aurastat VT *
auramode
aura - t
* aurastat V and aurastat VT are not recomended for use with TPxxx BC/BE models.
The HRVs are delivered with default factory settings these are detailed below. The information in the table supersedes any
default settings detailed in any other Product Manual.
Congurable Item B models BC & BE models BAR
SPEED 1 Setback Supply
18 % 25 % 88l/s
Extract
18 % 25 % 78l/s
SPEED 2 Continous Supply
40 % 40 % 179l/s
Extract
40 % 40 % 166l/s
SPEED 3 Boost Supply
70 % 70 % 311l/s
Extract
70 % 70 % 299l/s
SPEED 4
SUMMERboost®
Supply
100 % 100 % 392l/s
Extract
100 % 100 % 392l/s
Boost Overrun Kitchen
15 mins 15 mins 15 mins
Wet Room
15 mins 15 mins 15 mins
Boost Delay Timer Kitchen
0 mins 0 mins 0 mins
Wet Room
0 mins 0 mins 0 mins
Boost Inhibit On/O
O O O
Boost Inhibit Times Start
23 : 00 23 : 00 23 : 00
End
05 : 00 05 : 00 05 : 00
Filter Change Interval
12 months 12 months 12 months
Boost Overrun Timer Kitchen
15 mins 15 mins 15 mins
Wet Room
15 mins 15 mins 15 mins
Boost Delay Timer
0 mins 0 mins 0 mins
Boost Alert On/O
On On On
Boost Alert Timer
2 hours 2 hours 2 hours
Summer Mode
Enable/Disable
Disable Disable Disable
Summer Mode Extract
22 °C 22 °C 22 °C
Supply
18 °C 18 °C 18 °C
Supply Fan
Speed
0 % 0 % 0 %
Summer By Pass
Enable/Disable
Enable Enable Enable
Summer By Pass Extract
25 °C 25 °C 25 °C
Supply
18 °C 18 °C 18 °C