MAGLINK LX
Installation Manual
| Connections
Rev. 09,
– April 2016
Page 13 of 24
6.2
Connecting the XMT explosion execution
The image below shows how to connect your console to an XMT probe explosion:
The XMT model explosion probes must be connected in parallel to the console and directly to the
connector CN7 without passing through the intrinsically safe barrier.
In this case the barrier remains unused.
The following table lists the connections shown in the figure for connector CN7:
Connection
Specifications
CN7
Not used - Terminal 5
White (-0 V) - Terminal 4
Blue (RS485B) - Terminal 3
Brown (RS485A) - Terminal 2
Red (+ 12V) - Terminal 1

Other manuals for Tokheim ProGauge MAGLINK LX