6.7
Dipswitch Configuration
The following picture shows the inside of the upper side of the console if you observe the dipswitch you can
choose different configurations:
The following table shows the configuration of the dipswitch:
Dipswitch Description
1 OFF = single Gilbarco, ON = Double Gilbarco (required for DCD connections)
2
OFF = Internal inputs not available for alarms, but are used for other control functions
On = Internal inputs available for alarms
3
OFF = Automatic alarm mode off
ON = Anti-theft mode (Dipsw 2 must be OFF)
With 3 + 12 V DC CN10 connection Terminal and 1 0 V DC Terminal
4 OFF = Relay in normal mode, ON = Relay in reverse
6
General Reset
(Turn off the console, switch to ON, turn on the console, wait for the display
cursor in the top left to flash, turn off the console, switch to Off, turn on the console)
ATTENTION: The general reset results in loss of all configuration data, the
historical, alarms, delivery and reconciliations
7 OFF = Reconciliation deactivated, ON = Reconciliation activated
Dipswitchs not mentioned are reserved for future use