EasyManua.ls Logo

Tokheim ProGauge MAGLINK LX - Connect the Console to the Management Systems

Tokheim ProGauge MAGLINK LX
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAGLINK LX
Installation Manual
| Connections
Rev. 09,
– April 2016
Page 19 of 24
6.10
Connect the console to the management systems
The console can be connected via the RS232 port Com 1 on the following operating systems:
DIALOG
DOMS
FUEL POS
(VR350
Interface)
GILBARCO
ORPAK
PIGNONE
RETALIX
Probe emulation
The following picture shows the connection for the DIALOG Fuel management system:
The following table lists the connection for the DIALOG Fuel management system:
Console (DB9)
DIALOG system (DB9)
PIN 2
PIN 2
PIN 3
PIN 3
PIN 5
PIN 5
---
Connect PIN 4 with PIN 6
The following picture shows the connection for the GILBARCO Fuel management system:
The following table lists the connection for the GILBARCO Fuel management system:
Console (DB9)
GILBARCO system (RJ45)
PIN 2
PIN 8
PIN 3
PIN 1
PIN 5
PIN 4

Other manuals for Tokheim ProGauge MAGLINK LX