ACE-tronics G9 ASD Installation and Operation Manual 117
RX Input Point 2 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the RX input level that is associated with RX Input Point 2
Frequency (
F219) when operating in the Speed control mode or is associated
with the RX Input Point 2 Rate (F221) when operating in the Torque Control
mode.
This value is entered as -100% to +100% of the RX input signal range.
See RX Input Point 1 Setting (F216) for additional information on this setting
when used for Speed control.
See RX Input Point 1 Rate (F220) for additional information on this setting
when used for Torque Control.
Direct Access Number F218
Parameter Type — Numerical
Factory Default — +100
Changeable During RunYes
Minimum — -100.0
Maximum — +100.0
Units — %
RX Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets RX Input Point 2 Frequency and is the frequency that is
associated with the setting of RX Input Point 2 Setting (
F218) when operating
in the Speed Control mode.
See RX Input Point 1 Setting (F216) for additional information on this setting.
Direct Access Number F219
Parameter Type — Numerical
Factory Default 60.00
Changeable During RunYes
Minimum — 0.00.
Maximum — Max. Freq. (F011)
Units — Hz
F218 F219